Basler DECS-200-2L | Digital Excitation Control System | Synchronous Generator Voltage Regulator
The Basler DECS-200-2L is a robust Digital Excitation Control System engineered to manage the excitation current and output voltage of synchronous generators. This model is part of the DECS-200 series and features Line-to-Line (2L) sensing, making it ideal for single-phase systems or configurations where three-phase sensing is unnecessary. Its precision and reliability make it a perfect choice for industrial, utility, and marine applications where stable voltage regulation is critical.
As a microprocessor-based controller, the DECS-200-2L offers advanced PID tuning, extensive protection mechanisms, and a variety of communication protocols, ensuring optimal performance in a wide range of power generation systems. Whether you are managing large motors in an industrial cogeneration plant or maintaining stable output for marine generators, this system provides exceptional control.
| Feature | Specification |
|---|---|
| Model Number | DECS-200-2L |
| Input Power (Operating) | 100 to 240 VAC or 125/250 VDC |
| Excitation Output | 63 VDC @ 15 A (Continuous); 120 VDC @ 30 A (Forcing) |
| Voltage Sensing | 100 to 600 VAC, Single-Phase (Line-to-Line) |
| Current Sensing | 1 A or 5 A CT (Current Transformer) secondary |
| Regulation Accuracy | ±0.25% of Voltage Setpoint |
| Frequency Range | 45 Hz to 66 Hz |
| Communication | RS-232, RS-485 (Modbus RTU), CANbus |
| Enclosure Rating | IP20 (Finger-Safe) |
The DECS-200-2L is designed to adapt to various operational requirements:
AVR (Automatic Voltage Regulation): Ensures consistent terminal voltage across load changes.
FCR (Field Current Regulation): Maintains a constant manual excitation current.
Var/PF Control: Controls reactive power or Power Factor when operating in parallel with the grid.
To safeguard the system and ensure reliable performance, the DECS-200-2L includes:
Overexcitation Limiting (OEL): Prevents overheating of the field windings.
Underexcitation Limiting (UEL): Ensures generator synchronization with the grid.
Overvoltage/Undervoltage Protection: Instantaneous and time-delayed trips for overvoltage or undervoltage conditions.
Loss of Sensing Protection: Ensures safe operation in case of sensing failure.
The DECS-200-2L includes a Soft Start feature that gradually increases the voltage during startup, reducing mechanical and electrical stress on the generator and associated components.
Configured through Basler's BESTCOMS™ software, the DECS-200-2L allows engineers to monitor real-time metering, download event logs, and fine-tune system performance through Autotune features.
Mounting: The DECS-200-2L is typically installed on a sub-panel within the generator’s control switchgear.
Sensing Connections: For precise voltage regulation, use high-quality Potential Transformers (PTs) for Line-to-Line sensing.
Heat Dissipation: The unit's 15A continuous output requires proper mounting with adequate vertical clearance for efficient natural convection cooling.
Industrial Cogeneration: Ideal for systems where load variations are common, such as factories and large manufacturing plants.
Prime Power: Perfect for remote microgrid applications where consistent power stability is essential.
Marine Power Systems: Designed to withstand the rigors of shipboard environments, ensuring reliable operation of marine generators.
Ships within 48 hours · Estimated delivery Aug 2 - Aug 7
US$40
Get nowSign up to your membership to get coupons up to
15%
Get nowOpportunity to enjoy order discount up to 15% off
Top-Converting Item to Boost Your Average Order