The Wilkins 6-ZW209 is a pilot operated pressure reducing valve designed to reduce high inlet pressures to safe, stable outlet pressures in commercial and industrial water systems.
Key Specifications:
Other Related Variants:
Materials:
The recommended installation orientation for the Zurn 6-ZW209 is horizontal with the valve cover up. 6 Inches and larger valves should only be installed horizontally with the valve cover up due to the difficulty of properly bleeding air out of the cover and performing maintenance on valves installed in the vertical orientation. The valve should be installed with inlet and outlet shut-off valves for proper system control.
ANSI/AWWA C530; NSF/ANSI/CAN 61 (0.25% MAX. WEIGHTED AVERAGE LEAD CONTENT)
Features & Benefits:
Q: What is the minimum inlet pressure required for the Wilkins 6-ZW209?
A: The minimum inlet pressure is 10 psi higher than the set point or the additional body friction loss at intended flow, whichever is higher.
Q: Can the outlet pressure be adjusted on the Zurn 6-ZW209?
A: Yes, the pilot assembly is field adjustable from 15 psi to 120 psi, allowing for precise control of downstream pressure to meet specific application requirements.
Q: What components are included with the valve for maintenance purposes?
A: The valve comes standard with isolation valves on both inlet and outlet sides, inlet and outlet pressure gauges, a wye-type strainer, and a pilot assembly with all necessary copper tubing and brass fittings.
NOTICE: Do not use with water that is unsafe or of unknown quality without adequate disinfection either before or after the system.