Shopping security
The 1756-OB16I is a high-performance DC digital output module designed for the Rockwell ControlLogix series. It supports 16 individually isolated outputs, providing robust signal control in demanding automation systems. With fast response times, configurable fault states, and linear derating for high-temperature environments, this module ensures reliable operation in industrial applications.
The module meets UL, CSA, CE, ATEX, and FM certifications, making it suitable for hazardous locations and global deployment. It offers synchronization with the ControlLogix system clock, user-configurable states, and strong surge protection.
16 individually isolated outputs for precise control
Output voltage range: 10–30V DC
Output current:
Per point: 2A max @ 30°C, 1A max @ 60°C
Per module: 8A max @ 30°C, 4A max @ 60°C
Backplane current: 350 mA @ 5.1V DC, 2.5 mA @ 24V DC
Total backplane power: 1.8 W
Max power dissipation: 3.6 W @ 60°C
Thermal dissipation: 12.28 BTU/hr
Surge current: 4A for 10 ms per point, repeatable every 2 s
On-state voltage drop: 1.2V DC @ 2A
Off-state leakage current: 0.5 mA max per point
Output delay: OFF→ON: 1 ms, ON→OFF: 2 ms
Minimum load current: 1 mA per point
| Specification | Value |
|---|---|
| Number of Outputs | 16 (individually isolated) |
| Module Location | 1756 ControlLogix Chassis |
| Backplane Current | 350 mA @ 5.1V DC, 2.5 mA @ 24V DC (1.8 W total) |
| Power Dissipation | 3.6 W @ 60°C |
| Thermal Dissipation | 12.28 BTU/hr |
| Output Voltage Range | 10–30V DC |
| Surge Current | 4A for 10 ms, repeatable every 2 s |
| Isolation Voltage | 2546V DC tested, 250V AC continuous |
| Minimum Load Current | 1 mA per point |
| On-State Voltage Drop | 1.2V DC @ 2A |
| Output Delay | OFF→ON: 1 ms; ON→OFF: 2 ms |
| Module Keying | Software configurable |
| Field Wiring | 36-position RTB (1756-TBCH or 1756-TBS6H) |
| Wire Size | #22 to #14 AWG (0.324–2.08 mm²) stranded |
| Enclosure Type | Open-style |
Operating temperature: 0–60°C (32–140°F)
Storage temperature: –40–85°C (–40–185°F)
Relative humidity: 5–95% non-condensing
Vibration: 2 g @ 10–500 Hz
Operating shock: 30 g; Non-operating: 50 g
ESD immunity: 6 kV contact, 8 kV air discharge
Radiated RF immunity: 10 V/m, 30 MHz–2000 MHz
Surge immunity: ±1 kV line-line, ±2 kV line-earth
UL & CSA: Listed for industrial control equipment and Class I, Div 2
CE: EMC & Industrial Emissions compliant
FM: Approved for Class I Division 2
C-Tick / ATEX: Industrial and potentially explosive atmospheres compliance