Shopping security
The ABB REB500BU (Part Number: 1KHL160006R0001H) is a decentralized Bay Unit designed for busbar protection in medium-, high-, and extra-high-voltage substations. It provides fast, reliable protection, control, and supervision of single busbars, suitable for high-impedance applications in utility and industrial power networks. This module also supports restricted earth-fault and residual earth-fault protection for generators, motors, transformers, and reactors.
The REB500BU serves as the local intelligence of a distributed busbar protection scheme, acquiring analog signals, monitoring breaker and isolator status, and transmitting data to a Central Unit (CU) for coordinated control.
Sub-cycle fault tripping for rapid response, typically within 15–20 ms, ensuring minimal disruption to primary equipment
Low-impedance differential protection isolates only the faulted section of the busbar
Breaker Failure Protection (BFP): Monitors the tripping response of circuit breakers
End-Fault Detection: Protects the line between CT and breaker
Overcurrent and Overvoltage Backup: Provides independent back-up protection
Disturbance Recording: Integrated memory for event waveform capture and analysis
IEC 61850 Compliance: Full MMS and GOOSE support for digital substation integration
High-Speed Data Exchange: Compatible with process bus architectures
Redundant Networking: PRP (Parallel Redundancy Protocol) support ensures continuous communication even if a network path fails
Multiple binary inputs for breaker/isolator status and fast-acting relay outputs for tripping
Self-supervision of hardware and software health with immediate alarm generation
Operating Temperature: –25°C to +55°C (standard) or up to +70°C in specific configurations
Optimized for use with standard CTs, reducing system complexity and cost
| Feature | Specification |
|---|---|
| Model | REB500BU |
| Part Number | 1KHL160006R0001H |
| Application | Distributed Busbar & Breaker Failure Protection |
| Nominal Frequency | 50 Hz, 60 Hz, or 16.7 Hz |
| Communication | Ethernet (RJ45 or Fiber Optic), IEC 61850 |
| Measurement | 16-bit A/D conversion for CT/VT inputs |
| Mounting | Rack or panel mount, 6U height typical |
| Dimensions | Width: Frame 177 mm, Case 164 mm; Height: Frame 177 mm, Case 160 mm; Depth: 201 mm (153 + 48 mm) |
| Weight | Complete unit: 4.1 kg; Plug-in module: 2.1 kg |
| Auxiliary Voltage | Type 1: AC 100–240 V, 50/60 Hz; Type 2: DC 24–250 V |
| Power Consumption | Type 1: <15 W max; Type 2: <10.8 W max |
| Response Time | Maximum 50 ms at nominal voltage |
| Fuse | T4A/250 V |
Substation busbar protection (MV, HV, EHV)
Generator, transformer, motor, and reactor earth-fault monitoring
Breaker failure detection and backup protection
Digital substation integration with IEC 61850 networks
Q: What role does the REB500BU play in a substation?
A: It acts as the local Bay Unit, monitoring currents, voltages, and breaker status, while supporting protection logic independently or in coordination with a Central Unit.
Q: Is it compatible with IEC 61850 systems?
A: Yes, it supports IEC 61850-8-1 with MMS and GOOSE protocols for seamless digital substation integration.
Q: What are the typical response times for fault detection?
A: Fault detection and tripping typically occur within 15–20 milliseconds.
Ships within 48 hours · Estimated delivery Jul 20 - Jul 25